Calculators / Wire Voltage Drop Calculator
Wire Voltage Drop Calculator
Estimate conductor resistance and voltage drop for a single-phase or balanced three-phase wire run.
Inputs
Example values are prefilled. Enter your own values, then calculate.
Result
Enter the values above and calculate. Results clear when an input changes.
How to use
Start with the example values, replace them with your own, and press Calculate. Change any input to clear the previous result. You can copy the result or a link that restores your inputs.
Formula and assumptions
R = ρ × one-way length / area. Single phase: ΔV = 2 × I × R. Three phase: ΔV = √3 × I × R.
Copper ρ = 0.01724 and aluminum ρ = 0.0282 Ω·mm²/m at about 20 °C. This unity-power-factor resistive estimate ignores AC reactance, conductor heating, joints, and installation conditions. Verify final design with local code.
Worked example
A 230 V single-phase, 10 A load on 30 m of 2.5 mm² copper gives about 4.14 V drop, or 1.80%, using 20 °C resistivity.
Understand the result
Calculated values are estimates from the stated model. Check equipment ratings and installation conditions before using them in a real circuit.